Hot Water Recirculating System

Hot Water Recirculating System

10000.00 - 100000.00 INR/Piece

Product Details:

X

Hot Water Recirculating System Price And Quantity

  • 10000.00 - 100000.00 INR/Piece
  • 1 Piece

Hot Water Recirculating System Trade Information

  • 1 Piece Per Day
  • 1 Days

Product Description

Stop Waiting! Start Using!

Have you ever waited for hot water to reach the taps of your washroom? Whenever one waits for the water to get hot and reach the faucets, this process not only consumes time but energy and money also. The wait to get hot water instantly is over with Mircrotech’s Hot Water Recirculating System. This system helps in eliminating the wastage of money that is spent over the drain for obtaining hot water. It can be easily installed within an hour requiring two valves, shut-off and in-line air valves. Depending upon the type of application, requirements of installations may vary.

Key Benefits:

  • Below cited are the benefits that we get from installing Hot Water Recirculating System at our places:
  • Pump can be directly mounted onto the water heater for obtaining instant hot water to the faucet
  • In comparison to other low pressure water lines, the mentioned system quickly delivers water
  • Connects readily to the existing plumbing by eliminating the requirement of addition piping
  • Dual setting programmable timer for activating the pump during the requirement only

Specification

Abnormal Condition

Safety Action

Low Thermic Fluid Level in Expansion Tank

Level Switch actuated at expansion tank cuts of the ID Fan / FD Fan.

Low Thermic Fluid Flow

Differential pressure switch (DPS) across inlet and outlet headers cuts of the ID Fan slowing down combustion

Thermic Fluid system pressure high due to system valves closure etc.

Pressure switch cuts of ID Fan and alarm. Safety relief valve (Optional) to be provided in the system piping so as to by pass the oil.

Thermic Fluid Temperature High

Digital Temperature cuts of ID fan at set point

Coil Chocking

Differential pressure Switch (DPS) across system cuts of the ID Fan Slowing down combustion

Thermic Fluid Motor Trip

Electrical Interlock cuts of fans

Power Failure

Diesel Engine (Optional) keeps thermic fluid moving to avoid overheating and overflow of oil. Exhaust with Damper provided on furnace to drive away hot gases directly.

 